On this page 13 sections
- 01What Changed on 29 May 2025
- 02The Conditions in Full
- 03The Noise Test: MCS 020(a)
- 04Failed the Noise Check? What to Do
- 05Air-to-Air Units and Cooling
- 06Flats
- 07Ground-Source and Water-Source Heat Pumps
- 08Neighbours and Complaints
- 09Installers
- 10Listed Buildings and Conservation Areas
- 11Wales, Scotland and Northern Ireland
- 12Frequently Asked Questions
- 13Area Examples
You do not need planning permission for an air source heat pump at a house in England if it fits Class G of Part 14 of the GPDO: the outdoor unit is no more than 1.5 cubic metres, there are no more than one (two on a detached house), it passes the MCS 020(a) noise calculation (37 dB(A) at neighbours' windows), and it is not on a pitched roof, a listed building or a highway-facing wall in a conservation area. The old rule that a heat pump must be 1 metre from the boundary was removed on 29 May 2025. This guide is current as at 20 October 2026.
Before you install near a boundary, or to see how your council treats similar installations: Search planning applications near you free ->
What Changed on 29 May 2025
The Town and Country Planning (General Permitted Development) (England) (Amendment) Order 2025 (SI 2025/560), articles 5 and 6, rewrote parts of Class G. Before, the right was limited to a single unit of 0.6 cubic metres or less, 1 metre from the boundary, used solely for heating, complying with the MCS Planning Standards "or equivalent standards" (text in force on 28 May 2025). Now:
| Rule | Before 29 May 2025 | From 29 May 2025 |
|---|---|---|
| Distance from boundary | Not within 1 m of the boundary of the curtilage | No boundary-distance rule (G.2(e) omitted) |
| Number of pumps | One | One on a non-detached house or block of flats; two on a detached house (G.2(a)) |
| Outdoor unit size | 0.6 m³ | 1.5 m³ for a dwellinghouse; 0.6 m³ for a block of flats (G.2(d)) |
| Noise standard | MCS Planning Standards "or equivalent standards" | MCS 020(a) only (G.1; para P); "equivalent standards" saved until 28 May 2026 (art 7) |
| Use | "used solely for heating purposes" | "not solely used for the purpose of cooling" (G.3(aa)): air-to-air units that heat and cool now qualify |
The transitional saving in article 7 let an installation that relied on "equivalent standards" instead of the MCS standard go ahead until the end of 28 May 2026. Since 29 May 2026, MCS 020(a) is the only route. If you read that heat pumps "must be 1 metre from the boundary", it was true until 28 May 2025 and is not true now.
The Conditions in Full
Under Class G, development is not permitted unless the pump complies with the MCS Planning Standards (G.1), and is not permitted if (G.2):
- it would mean more than one pump on or in the curtilage of a non-detached house or block of flats, or more than two on a detached house (a; "detached" means not sharing a party wall with a neighbouring building, para P);
- a wind turbine is on the same building, or a stand-alone wind turbine is in the curtilage (b, c);
- the outdoor compressor unit, including any housing, exceeds 1.5 cubic metres (dwellinghouse) or 0.6 cubic metres (block of flats) (d);
- it is on a pitched roof (f), or on a flat roof within 1 metre of the external edge (g);
- it is on a scheduled monument site (h), or on or in the curtilage of a listed building (i);
- in a conservation area or World Heritage Site, it is on a wall or roof that fronts a highway, or nearer the highway than the part of the house nearest to it (j);
- elsewhere, it is on a wall that fronts a highway and above the level of the ground floor storey (k).
The conditions (G.3): not solely used for cooling; so far as practicable sited to minimise its effect on the external appearance of the building and on the amenity of the area; removed as soon as reasonably practicable when no longer needed.
Permitted development rights can still be withdrawn by an article 4 direction or by a condition on the house's own planning permission (GPDO art 4, art 3(4)); see permitted development rights explained for how to check. A "block of flats" means a building consisting wholly of flats (para P).
The Noise Test: MCS 020(a)
MCS 020(a) is named in the Order itself (para P); the version referred to when the Order was amended is Issue 1.1 of 14 April 2025. It is a calculation, completed for each assessment position:
- Take the manufacturer's A-weighted sound power level for the unit.
- Apply the unit's directivity, the distance to the assessment position and any barrier correction.
- Compare the result with the permitted development limit of 37 dB LAeq,5mins.
An "assessment position" is a position 1 metre outside the centre of any door or window to a habitable room of a neighbouring property; the standard says to consider neighbours on all sides, because the nearest position is not always the loudest. Where there are two heat pumps, the combined level at each position is tested. If the calculated level at any position is above 37.0 dB(A), "the heat pump will not comply with the permitted development noise limit and is not permitted development". Compliance with MCS 020(a) alone does not give permitted development rights; the other conditions must also be met (para 1.3). The contractor must keep one completed copy and give another to you (para 1.7), so ask for it.
Failed the Noise Check? What to Do
A failed calculation means Class G does not apply to that installation. You have three options:
- Change the installation and recalculate. The standard itself suggests adjustments such as moving the heat pump. A different model with a lower sound power level, or a barrier, changes the inputs.
- Apply for planning permission. For a house, this is a householder application decided on its merits, with noise a material consideration. For a flat or block of flats it is not a householder application (DMPO art 2(1)), and a different fee applies, so ask the council. For a house, the fee from 1 April 2026 is £548 where the pump is an alteration to the house, or £272 where it is an operation within the curtilage (MHCLG fee table, categories 6 and 7); the council decides the category, so confirm before paying. The council must decide a valid application within 8 weeks unless you agree a longer period in writing (DMPO art 34(2)(b), (c)). A refusal can be appealed within 12 weeks for a householder appeal (art 37(2)). What to send: plans showing the unit's position and its distance to neighbours' habitable-room windows, the unit's make, model and manufacturer's sound data, and your MCS 020(a) tables with any mitigation. Check your council's validation list for what it requires.
- Do not install first and apply later. If you install something that is not permitted development, you can apply afterwards under section 73A of the 1990 Act, but you carry the risk of refusal. See retrospective planning permission.
Air-to-Air Units and Cooling
Since 29 May 2025 a unit that heats and cools qualifies, because G.3(aa) only requires that the pump is "not solely used for the purpose of cooling". The Order does not define "air source heat pump", but the government's explanatory memorandum to SI 2025/560 says (para 5.13) that the change "will allow for air-to-air heat pumps to benefit from the permitted development right", and (para 7.10) that the MCS Planning Standard "also applies to ASHPs that can provide cooling". A cooling-only unit is outside Class G. See Do I Need Planning Permission for Air Conditioning? for that analysis, including commercial premises.
Flats
For a block of flats the unit may not exceed 0.6 cubic metres, and only one pump is allowed on or in the curtilage of the whole block (G.2(a), (d)). A flat above a shop is not in a "block of flats", so Class G does not apply. Leases, freeholder consent, fire safety and noise covenants are separate from planning.
Ground-Source and Water-Source Heat Pumps
Class C and Class D grant the right to install a microgeneration ground source or water source heat pump within the curtilage of a house or block of flats, and the text of each contains no further limits or conditions. That is a statement about planning only; a borehole, trench or watercourse use can involve other regimes, and a listed building may still need listed building consent. Ask your installer.
Neighbours and Complaints
Neighbours cannot object to permitted development. If an application is needed, they can comment on noise, siting and visual impact. After installation, a noise complaint goes to environmental health: under section 79(1)(g) of the Environmental Protection Act 1990, "noise emitted from premises so as to be prejudicial to health or a nuisance" is a statutory nuisance, and the council must take reasonably practicable steps to investigate a complaint from a resident of its area. Passing MCS 020(a) does not make section 79 irrelevant. See planning objection: noise and disturbance.
Installers
Class G compliance is evidenced by the MCS 020(a) tables; refrigerant handling is a separate legal matter. Government guidance says you must have your own F gas qualification to work on equipment containing F gas (GOV.UK, Qualifications to work with F gas). Ask for both.
Listed Buildings and Conservation Areas
A listed building, or land in a listed building's curtilage, is outside Class G (G.2(i)). Fixings and pipe routes can also need listed building consent. See planning permission for listed buildings, conservation areas and planning, solar panels for the solar equivalent, and do I need planning permission for a flue or chimney if you are fitting a wood burner or biomass flue instead.
Wales, Scotland and Northern Ireland
This guide is about England. SI 2025/560 amends the England Order.
- Wales: air source heat pumps are Class G of Part 40 of Schedule 2 to the 1995 Order. Since 1 June 2026 (WSI 2026/79) Wales has no boundary-distance rule either: the old Welsh rule that no part of the pump could be within 3 metres of the boundary was removed. The changes also allowed one pump (two on a detached house) of up to 1.5 cubic metres, and allowed a unit on a highway-facing wall at ground-floor level outside conservation areas (in a conservation area, not on a highway-facing wall or roof). "Or equivalent standards" was deleted (MCS 020(a) only), and "used solely for heating" was replaced by "must not be solely used for cooling". Pitched roofs, listed buildings and scheduled monuments remain excluded (Welsh Government summary). The Welsh class mentions a 1 cubic metre limit for blocks of flats, but the grant itself still refers only to a dwellinghouse, which in Wales now excludes a building containing flats, so flat owners should check with the council.
- Scotland: Class 6H allows one air source heat pump on a dwelling (including a flat) or in its curtilage. There is no boundary-distance rule. A unit fixed to the building may not protrude more than 1 metre. One in the garden may not exceed 3 metres in height or sit forward of a road-facing front or side wall. In a conservation area, a unit on the building must be at ground-floor level on the rear elevation. None is allowed in a World Heritage Site or the curtilage of a listed building. The pump must be "used only for the purpose of providing domestic heating or hot water" and meet MCS or equivalent standards (Planning circular 1/2024, section 6). Ground and water source pumps are Classes 6D and 6E.
- Northern Ireland: Part 2, Class G of the 2015 Order allows one pump, not within 1 metre of the boundary of another dwelling, no more than 3 metres high, not on a roof, and used to provide heat.
Area Examples
Terraced layouts and close boundaries make noise siting important in places like Bristol, Sheffield and Chelmsford; in Cornwall, listed cottages and conservation areas make visual siting more sensitive. Search nearby applications to see how your council treats similar installations. If a unit has been installed without the right permission, see planning enforcement: when rules are broken.
Frequently Asked Questions
Do I need planning permission for an air source heat pump?
Often not: if it meets Class G (1.5 m³ unit, one or two pumps, MCS 020(a), siting limits), it is permitted development.
Is there still a 1 metre boundary rule?
No. It was omitted from 29 May 2025.
What if my heat pump fails the noise calculation?
It is not permitted development. Redesign and recalculate, or apply (£548 or £272).
Can I put a heat pump on the roof?
Not on a pitched roof. On a flat roof, keep at least 1 metre from the edge.
Can I install a heat pump in a conservation area?
Yes, but not on a wall or roof fronting a highway, and not nearer the highway than the house.
Do I need permission to replace an old heat pump?
Not if the new unit meets the current Class G limits (it covers installation, alteration or replacement). If the old unit was approved by an application, check that permission for conditions.
Can my neighbour object to my heat pump?
Not to permitted development; they can complain about noise as a statutory nuisance.
Going green? Get quotes from MCS-certified installers
We're onboarding accredited renewables installers now — leave your details and we'll match you locally.
Disclaimer: PlanWatch provides general information about UK planning processes. This content is not legal advice. Planning law is complex and varies by local authority. Consult a qualified planning consultant or solicitor for advice specific to your situation.